Medium voltage AWA armoured cable is an insulated power cable with aluminium wire armour, commonly specified for single-core AC installations where mechanical protection is required. To select it correctly, confirm the system voltage, conductor material and size, insulation, screen construction, installation conditions, and applicable cable standard before requesting a quotation. AWA is often considered for single-core circuits because its non-magnetic aluminium armour avoids some of the induced-current and heating concerns associated with magnetic steel armour around a single AC conductor. The exact design must still be checked against the project specification and installation method.
You can find more information on our web, so please take a look.
This guide is intended for electrical contractors, engineering consultants, procurement teams, distributors, and project owners evaluating medium voltage cable for utility, industrial, infrastructure, or commercial power systems. It is useful when preparing a new cable specification, comparing supplier proposals, or checking whether a quoted construction matches the design documents. It is not a substitute for electrical design review or the governing standards for a particular project. Confirm final cable selection with the responsible engineer and local requirements.
Medium voltage (MV) cable carries electrical power at a voltage level above typical low-voltage distribution, with the exact classification depending on the applicable standard and market. AWA describes aluminium wire armour, a protective layer made from aluminium wires laid around the cable core or cores. An MV cable also includes a conductor, insulation, electric-field control layers, metallic screen, and outer sheath, with details varying by design. The armour primarily provides mechanical protection; it should not be treated as a replacement for the metallic screen or protective earthing arrangement.
The conductor carries current and may be copper or aluminium, subject to electrical design and project requirements. MV insulation is commonly cross-linked polyethylene (XLPE) or another specified insulation system, with semiconductive layers and a metallic screen used to manage the electric field and provide a path for fault current as designed. The outer sheath protects the assembly from environmental and handling conditions specified for the installation. AWA adds mechanical protection, while the complete cable construction must be coordinated with glands, joints, terminations, and bonding practices.
A cable designation is only useful when its components and ratings are clear. The following values are examples to help frame a specification, not a universal recommendation: a project might use a 6.35/11 kV cable rating, XLPE insulation with a 90°C maximum normal conductor operating temperature, or a conductor cross-section such as 35 mm². Actual voltage designations, permissible temperatures, and available sizes depend on the standard, cable design, and project conditions.
| Specification | What to define | Why it matters |
|---|---|---|
| Rated voltage | System voltage and cable U0/U (and Um, where applicable) | Ensures the insulation system matches the network and overvoltage requirements. |
| Conductor | Copper or aluminium, cross-sectional area, stranding, and conductor class | Affects current capacity, voltage drop, termination compatibility, and handling. |
| Insulation and screen | Insulation material and thickness, semiconductive layers, metallic screen material and area | Supports electrical performance and the specified earth-fault duty. |
| Armour and sheath | AWA wire design, sheath material, colour, and any additional protective layers | Addresses mechanical, moisture, chemical, and environmental exposure. |
| Standard and tests | Applicable standard, routine tests, and any project-specific inspection requirements | Establishes the compliance and documentation basis for acceptance. |
State the network voltage and the required cable voltage designation instead of asking for “medium voltage” cable alone. For example, 6.35/11 kV is one commonly encountered designation, but it is not suitable for every system or jurisdiction. Select copper or aluminium conductors based on the design’s current capacity, installation constraints, losses, and connection equipment. Confirm conductor size using the applicable ampacity method and project conditions rather than relying on a catalogue value without its assumptions.
Specify the metallic screen construction and cross-sectional area according to the required earth-fault current and duration, as well as the earthing and bonding design. AWA is commonly selected for single-core AC cables where non-magnetic armour is preferred, but the final armour and bonding arrangement should be reviewed for the circuit configuration. The sheath material should match the installation environment, including exposure to sunlight, moisture, oils, chemicals, or other conditions where relevant. If the cable is buried, installed in ducts, or routed in a hazardous or high-impact area, state those conditions explicitly.
You will get efficient and thoughtful service from Zhongdong Cable Co., Ltd..
Start with the physical route and operating environment, not just the electrical rating. Direct-buried routes may require attention to soil conditions, water exposure, mechanical protection, and installation pulling forces. Duct or trench installations have different heat dissipation and access considerations, while outdoor runs may need a sheath suitable for the expected weather and UV exposure. For industrial sites, document possible chemical contact, vibration, impact, and the requirements for cable support and termination access.
Single-core AWA cable is often evaluated for three-phase circuits using separate phase cables, but layout and magnetic effects depend on cable spacing, trefoil or flat formation, and bonding arrangements. Ask the design team to define the installation geometry and screen bonding method, as these can influence losses and thermal performance. Where a project uses multicore cable, compare the proposed armour type and standard construction with the specification rather than assuming AWA is the default. Manufacturer confirmation should be based on the complete design data.
A frequent mistake is requesting a cable based only on voltage and conductor size, leaving the screen, armour, sheath, or test requirements open to interpretation. Another is treating the cable’s normal operating temperature as permission to ignore installation-specific derating or emergency and short-circuit limits. Buyers may also overlook the interaction between single-core cable arrangement, armour, and bonding, or fail to verify that accessories suit the exact cable dimensions and construction. Resolve these points before purchase rather than relying on assumptions in a quotation.
The price of MV AWA cable depends on factors such as conductor material and size, rated voltage, screen and armour design, sheath specification, order quantity, drum length, and required documentation. Copper and aluminium options can have different material-cost exposure, while non-standard constructions or short production runs may affect quotation conditions. Minimum order quantities and lead times are supplier- and project-dependent; they should be confirmed against the required design, available production schedule, and delivery location. Request a quotation that identifies the quoted construction, quantity basis, delivery terms, and any exclusions.
Compare suppliers on technical clarity as well as price. Ask for a construction breakdown, applicable standard, product datasheet, declared test documentation, drum information, and a clear statement of deviations from the inquiry. Check that the supplier can discuss the proposed cable alongside the project’s voltage, installation, accessories, and documentation requirements. Where information is not available or is project-specific, request written clarification instead of assuming compliance.
Zhongdong Cable Co., Ltd. can be included in your supplier evaluation for medium voltage cable requirements. Share the technical schedule, drawings or route conditions, target quantity, destination, and requested delivery window so the team can assess the requested construction and clarify quotation details. A complete inquiry helps us identify open technical points early and provide a proposal aligned with your purchasing and engineering review process. Final selection and installation should remain subject to the project’s approved design and applicable requirements.
Medium voltage AWA armoured cable should be selected by matching its complete electrical and mechanical construction to the network, fault duty, installation route, and governing specification. The AWA layer can provide mechanical protection and is commonly considered for single-core AC designs, but it does not determine the cable’s voltage rating, screen duty, ampacity, or suitability on its own. Before requesting prices, prepare a schedule covering voltage, conductor, insulation, screen, armour, sheath, standards, accessories, quantity, and delivery needs. Send that information to Zhongdong Cable Co., Ltd. for a technical and commercial discussion, and have the final proposal reviewed against your project requirements.
Contact us to discuss your requirements of Medium Voltage AWA Armoured Cable. Our experienced sales team can help you identify the options that best suit your needs.