Choose between a 5P10 and a 5P20 protective current transformer (CT) by checking the maximum fault current the relay must measure and the CT’s total connected burden. Both have a 5P protection class, meaning the specified composite error limit is 5% at the accuracy limit factor (ALF), when tested under the applicable standard conditions. The difference is the ALF: a 5P10 CT is specified up to 10 times rated primary current, while a 5P20 CT is specified up to 20 times rated primary current. A 5P20 is not automatically the better choice; it must match the protection study, burden, and equipment requirements.
Click here to get more.
The marking on a protection CT combines its protection class and accuracy limit factor. In “5P10,” “5P” identifies the protection class and “10” indicates an ALF of 10. In “5P20,” the class remains 5P, but the ALF is 20.
For example, for a CT with a rated primary current of 100 A, an ALF of 10 corresponds to a stated accuracy limit primary current of 1,000 A. An ALF of 20 corresponds to 2,000 A. These figures describe the specified accuracy limit under stated conditions; they are not a guarantee that the CT will reproduce current accurately beyond that limit or under any burden.
For a 5P protection CT, the applicable specification limits composite error to 5% at the stated accuracy limit current and rated burden, subject to the relevant standard and test conditions. Composite error accounts for errors in reproducing the primary current, including the effects of ratio error and phase displacement. It does not mean that the CT has 5% error at every current, nor does it alone describe performance for every relay or fault waveform.
The ALF relates the accuracy limit primary current to the rated primary current. A higher ALF means the CT is specified to maintain its protection-class performance to a higher multiple of rated current at the stated burden. Because burden affects performance, the ALF marking should always be read together with the CT’s rated burden in volt-amperes (VA).
| Selection point | 5P10 | 5P20 |
|---|---|---|
| Protection class | 5P | 5P |
| Accuracy limit factor | 10 | 20 |
| Accuracy limit current | 10 times rated primary current | 20 times rated primary current |
| Typical selection consideration | May suit applications where the calculated fault-current multiple is within the specified limit | May be considered where a higher fault-current multiple must be covered |
This comparison assumes the same rated primary current, rated burden, and applicable test basis. A 5P20 designation does not remove the need to verify the CT’s ratio, secondary rating, burden, thermal and dynamic ratings, and system conditions. Always compare complete nameplate and procurement specifications rather than selecting by class marking alone.
Start with the protection scheme and the maximum fault current that the CT must reproduce for the connected relay or protection device. Use the project’s system study and relay requirements rather than estimating from normal load current. Consider the fault locations and operating conditions specified by the project, since the relevant current can vary across the installation.
Then compare the required primary current with the CT’s rated primary current to establish the fault-current multiple. If that required multiple exceeds 10, a 5P10 may not meet the stated ALF requirement at its rated burden. A 5P20 provides a higher specified limit, but the engineer should still verify that the selected CT meets the full application requirements.
Burden is the load connected to the CT secondary, expressed in VA at a specified secondary current. It can include relay or meter inputs, wiring, and other connected devices. Compare the estimated total burden with the CT’s rated burden and follow the project design and applicable standard when assessing performance.
Long secondary leads can add burden, so include their resistance in the calculation using the conductor size, circuit length, and secondary rating. Do not assume that a CT with a higher ALF marking will deliver that performance if the actual burden exceeds the rated value. If the burden is uncertain, ask the engineer or supplier to review the complete secondary circuit before ordering.
You will get efficient and thoughtful service from ANNEZEE.
Specify the primary-to-secondary ratio required by the system and confirm whether the protection equipment is designed for a 1 A or 5 A secondary. These are common CT secondary ratings, but the correct choice depends on the connected equipment and project specification. The CT, relay, and wiring must be compatible as a complete circuit.
Also confirm the number of cores and each core’s intended function. Protection and metering requirements may call for separate cores with different specifications. A protection-class marking should not be assumed to satisfy metering accuracy requirements.
Review rated insulation level, rated frequency, installation conditions, short-time thermal current, and dynamic current requirements against the project documents. These ratings address different aspects of suitability from the 5P class and ALF. The required values depend on the system design and must be confirmed by the responsible engineer.
For applications involving high fault currents or demanding protection coordination, ask whether the specified protection class and ALF are sufficient for the relay’s operating requirements. Some schemes may require a different CT class or a dedicated performance assessment. Do not treat 5P10 or 5P20 as a universal substitute for checking the protection design.
A 5P10 may be appropriate when the fault-current multiple required by the protection design remains within its specified accuracy limit and the rated burden is adequate. A 5P20 may be appropriate when the design requires a higher multiple, provided the ratio, burden, and other ratings also satisfy the application. Neither designation should be selected without checking the project’s fault study and relay requirements.
Where the required fault current approaches or exceeds the selected CT’s limit, ask the protection engineer to reassess the specification. Possible actions may include reviewing the ratio, burden, CT class, or protection scheme; the correct solution depends on the design. This check is especially important when the available fault current, lead length, or relay input burden is not yet confirmed.
To help a manufacturer or supplier evaluate your requirement, include the project’s technical details in the request for quotation. A clear specification helps reduce ambiguity during selection and purchasing. Share the following information where available:
The direct difference is the ALF: 5P10 is specified to its accuracy limit at 10 times rated primary current, while 5P20 is specified at 20 times rated primary current. Both are 5P protection CTs with a stated 5% composite error limit at the accuracy limit under applicable conditions. Select between them by calculating the required fault-current multiple and verifying rated burden, ratio, secondary rating, and all other project ratings.
Before issuing an order, have the protection design and secondary burden checked against the proposed CT specification. At ANNEZEE, we can review your RFQ information and discuss protective current transformer options, drawings, and configuration requirements. Send us the key electrical ratings and application details to request a quotation or a specification review.